Your location: Products >  Off Grid Inverter >  Middle Frequency Pure sine Wave Inverter >

TNP-50KW

TNP-50KW

TNP-50KW

Category:Middle Frequency Pure sine Wave Inverter
Technical Features: 1.Using the sixth generation efficient IPM intelligent module from Japanese Mitsubishi, high efficiency and stable performance. It with powerful protection function for short circuit, over load and over temperature which is more safe and reliable. It\'s service life can up to 15-20 years or more. 2.Intelligentized, modularized and simple structure design, very easy and convenient for maintenance. 3.Two kinds of start mode: Step Down Voltage Start and Variable Frequency Start. 4.The output frequency 50Hz/60Hz can be set via LCD panel. 5.The output voltage can be set. 6.The DC input voltage range can be set. over-voltage point, under-voltage point, over-voltage recovery point, under-voltage recovery point and under voltage recovery time all can be set via the LCD panel. 7.Using SVPWM space vector algorithms, high conversion efficiency, high instantaneous power and low losses, higher efficiency > 94%. 8.Pure sine wave output. with good transient response less than 50MS, little harmonic distortion, higher conversion efficiency and stable output voltage. 9.Low frequency transformer, which ensure the AC busbar and DC busbar are completely isolated to avoid interference, high efficiency and very little no-load loss. 10.Powerful data display and fault instruction function. LCD can display the DC input voltage, output frequency, phase voltage, phase current, AC bypass input voltage, output power KWH, time and date, temperature, fault code display. 11.Wide input voltage can be set according to customer’s requirement. Input voltage range can be selected from 100-400v or 200-600v or 400-850v. This wide voltage input off grid inverter can work without battery and solar charge controller, which save battery cost and same like with MPPT function can maximum make full use of solar power . 12.AC bypass input function optional: Battery Power Priority or AC Bypass Priority work mode can be set. 13.RS485 remote monitoring function optional 14.Solar charge controller and AC to DC battery charger built in optional for customer 15.Can be customized to customer’s specification. 16.European CE (EMC and LVD) certification, accredited by Australian CEC, ERAC energy network, meet UL1741 and CSA22.2 standard.

Detailed description

Model TNP-50KW
Isolation mode Low Frequency Transformer
DC Input Rated voltage (Vdc) 360V
Rated current(A) 139A
AC Output Rated output power 50KW
Output waveform Pure Sine Wave
Rated Voltage 380VAC±3%
Phases 3 phase 4 wire
Rated current(A) 76A (phase current)
Frequency 50Hz or 60Hz
Rated output voltage range (V) 380/400/415/440VAC optional
Power Factor(PF) 0.9
Overload Ability 150%, 5 seconds
Efficiency >93%
Waveform distortion rate (THD) <3%(Linear load)
Dynamic Response (0 to 100% load) 5%,≤50ms
Display LCD
Running mode Working continuously
Electrical insulation properties 2000Vac, 1 Minute
Protection Function Protection Input reverse polarity, under voltage, overvoltage, output over-current, short circuit, overheating etc.
Cooling method Fan-cooled
Short-circuit protection No automatic recovery, need to restart the machine
Working environment Noise ( 1 meter) ≤50dB
Degree of protection IP20(indoor)
Working Altitude(m) ≤2000
Working temperature -25~+55℃
relative humidity 0~90%,non-condensing
Mechanical dimension Depth* Width * Height 800x850x1200mm
Weight (Kg) 420Kg

Hotline:0086-13587756198